ABB Relion 650 Series Technical Manual page 318

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
initiate
block start
UnsucClByCBchk = CBcheck
Pulse STBRREC
(Closing)
52a
ANSI10000263 V1 EN-US
Figure 162: Issue of signal UNSUCCL, unsuccessful reclosing
10.3.6.10
Automatic continuation of the reclosing sequence
The auto-reclosing function can be programmed to proceed to the following reclosing shots (if
selected) even if the initiate signals are not received from the protection functions, but the
breaker is still not closed. This is done by setting parameter
tAutoContWait to the required delay for the function to proceed without a new initiate.
CLOSECB
52a
PICKUP
ANSI10000254 V1 EN-US
Figure 163: Automatic proceeding of shot 2 to 5
312
AND
OR
AND
0-tUnsucCl
CBclosed
0
AND
CBClosed
OR
© Copyright 2011 ABB Power Grids. All rights reserved
OR
AND
shot 0
AND
ANSI10000263-1-en.vsd
AutoCont = Enabled and
0-tAutoContWait
0
S
Q
R
AND
OR
1MRK 506 326-UUS B
UNSUCCL
S
R
GUID-71ECF4E5-7424-467F-A65F-8CB8D9D68E6B v1
AND
initiate
ANSI10000254-1-en.vsd
Line distance protection REL650
Technical manual