ABB Relion 650 Series Technical Manual page 603

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Section 20
20.1
Electromagnetic compatibility tests
Table 568: Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference tests
Conducted, common mode
Radiated, amplitude-
modulated
Fast transient disturbance tests
Communication ports
Other ports
Surge immunity test
Communication
Other ports
Power frequency (50 Hz) magnetic
field
3 s
Continuous
Power frequency immunity test
Table continues on next page
Line distance protection REL650
Technical manual
IED and functionality tests
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz and
f=1.4...2.7 GHz
4 kV
4 kV
1 kV line-to-ground
2 kV line-to-ground, 1 kV line-to-line
1000 A/m
100 A/m
© Copyright 2011 ABB Power Grids. All rights reserved
IED and functionality tests
GUID-2794AAD0-DBFE-476D-BAD1-A8D0ECFE9C9C v4
Reference
IEC 61000-4-18
IEC 60255-22-1, level 3
ANSI C37.90.1-2002
IEC 61000-4-2
IEC 60255-22-2, level 4
ANSI C37.90.3-2001
IEC 61000-4-6
IEC 60255-22-6, level 3
IEC 61000-4-3
IEC 60255-22-3, level 3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2002
IEC 61000-4-5
IEC 60255-22-5, level 3/2
IEC 61000-4-8, level 5
IEC 60255-22-7, class A
IEC 61000-4-16
Section 20