ABB Relion 650 Series Technical Manual page 322

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
10.4.2.5
Settings
Table 236: QCBAY Non group settings (basic)
Name
Values (Range)
AllPSTOValid
Priority
No priority
10.4.3
Local remote LOCREM
10.4.3.1
Identification
Function description
Local remote
10.4.3.2
Functionality
The signals from the local HMI or from an external local/remote switch are applied via the function
blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY) function block. A parameter in
function block LOCREM is set to choose if the switch signals are coming from the local HMI or
from an external hardware switch connected via binary inputs.
10.4.3.3
Function block
LOCREM
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL
IEC09000076_1_en.vsd
IEC09000076 V1 EN-US
Figure 166: LOCREM function block
10.4.3.4
Signals
Table 237: LOCREM Input signals
Name
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL
316
Unit
Step
-
-
IEC 61850
identification
LOCREM
OFF
LOCAL
REMOTE
VALID
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
INTEGER
0
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Priority
Priority of originators
IEC 60617
identification
-
Description
Disable control
Local in control
Remote in control
LHMI control
1MRK 506 326-UUS B
PID-1959-SETTINGS v5
GUID-CBF253B8-8F35-409C-BB8B-2DAC0CEEB8C6 v1
ANSI/IEEE C37.2
device number
-
GUID-4FFF1093-E167-4079-91CA-A48F3801AF4E v1
PID-1826-INPUTSIGNALS v5
Line distance protection REL650
Technical manual
M17086-3 v4