ABB Relion 650 Series Technical Manual page 301

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Name
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
10.2.5
Settings
Table 226: SMBRREC (79) Group settings (basic)
Name
Values (Range)
Operation
Disabled
External ctrl
Enabled
t1 3Ph
0.000 - 60.000
tReset
0.00 - 6000.00
tSync
0.00 - 6000.00
tTrip
0.000 - 60.000
tCBClosedMin
0.00 - 6000.00
tUnsucCl
0.00 - 6000.00
Priority
None
Low
High
tWaitForMaster
0.00 - 6000.00
Table 227: SMBRREC (79) Group settings (advanced)
Name
Values (Range)
NoOfShots
1
2
3
4
5
StartByCBOpen
Disabled
Enabled
CBAuxContType
NormClosed
NormOpen
CBReadyType
CO
OCO
t2 3Ph
0.00 - 6000.00
t3 3Ph
0.00 - 6000.00
t4 3Ph
0.00 - 6000.00
Table continues on next page
Line distance protection REL650
Technical manual
Type
Description
INTEGER
Counting the number of three-phase reclosing shot 3
INTEGER
Counting the number of three-phase reclosing shot 4
INTEGER
Counting the number of three-phase reclosing shot 5
INTEGER
Counting total number of reclosing shots
Unit
Step
-
-
s
0.001
s
0.01
s
0.01
s
0.001
s
0.01
s
0.01
-
-
s
0.01
Unit
Step
-
-
-
-
-
-
-
-
s
0.01
s
0.01
s
0.01
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
External ctrl
Disable/ExternalCtrl/Enable
6.000
Open time for shot 1, delayed reclosing
3ph
60.00
Duration of the reset time
30.00
Maximum wait time for synchronism-check
OK
0.200
Maximum trip pulse duration
5.00
Minimum time that CB must be closed
before new sequence allows
30.00
Wait time for CB before indicating
Unsuccessful/Successful
None
Priority selection between adjacent
terminals None/Low/High
60.00
Maximum wait time for release from
Master
Default
Description
1
Maximum number of reclosing shots 1-5
Disabled
To be set ON if AR is to be started by CB
open position
NormOpen
Select CB auxilary contact type NC/NO for
CBPOS input
CO
Select type of circuit breaker ready signal
CO/OCO
30.00
Open time for shot 2, three-phase
30.00
Open time for shot 3, three-phase
30.00
Open time for shot 4, three-phase
Section 10
Control
PID-1122-SETTINGS v6
295

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents