Section 15
Station communication
Table 484: GOOSEMVRCV Output signals
Name
MVOUT
DATAVALID
COMMVALID
TEST
15.7.5
Settings
Table 485: GOOSEMVRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
15.7.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
15.8
GOOSE function block to receive a single point value
GOOSESPRCV
15.8.1
Identification
Function description
GOOSE function block to receive a
single point value
530
Type
REAL
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
-
-
The input of this GOOSE block must be crossed in the SMT to receive the float
values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
IEC 61850
identification
GOOSESPRCV
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Measurand value output
Data valid for measurand value output
Communication valid for measurand value output
Test output
Default
Description
Disabled
Operation Enable/Disable
IEC 60617
identification
-
1MRK 506 326-UUS B
PID-2530-OUTPUTSIGNALS v6
PID-2530-SETTINGS v6
GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v1
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1
ANSI/IEEE C37.2
device number
-
Line distance protection REL650
Technical manual