ABB Relion 650 Series Technical Manual page 560

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 16
Basic IED functions
16.5.3
Function block
INPUT
IEC09000219 V1 EN-US
Figure 290: TESTMODE function block
16.5.4
Signals
Table 507: TESTMODE Input signals
Name
INPUT
Table 508: TESTMODE Output signals
Name
ACTIVE
OUTPUT
SETTING
NOEVENT
16.5.5
Settings
Table 509: TESTMODE Non group settings (basic)
Name
Values (Range)
TestMode
Disabled
Enabled
EventDisable
Disabled
Enabled
CmdTestBit
Off
On
16.5.6
Operation principle
Put the IED into test mode to test functions in the IED. Set the IED in test mode by
554
TESTMODE
ACTIVE
OUTPUT
SETTING
NOEVENT
IEC09000219-1.vsd
Type
Default
BOOLEAN
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
-
-
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Sets terminal in test mode when active
Description
IED in test mode when active
Test input is active
Test mode setting is (Enabled) or not (Disabled)
Event disabled during testmode
Step
Default
-
Disabled
-
Disabled
-
Off
1MRK 506 326-UUS B
GUID-551B53B7-5D36-4DB8-BEA6-20AAC0525DFA v1
GUID-283C6180-A48B-413C-A2BF-9E15CF8B5D4E v1
Description
Test mode in operation (Enabled) or not
(Disabled)
Event disable during testmode
Command bit for test required or not
during testmode
Line distance protection REL650
Technical manual
SEMOD54888-4 v5
PID-1795-INPUTSIGNALS v7
PID-1795-OUTPUTSIGNALS v7
PID-1795-SETTINGS v7
IP12116-1 v3
M12015-4 v7

Advertisement