1MRK 506 326-UUS B
15.8.2
Functionality
GOOSESPRCV is used to receive a single point value from the sender using IEC61850 protocol over
GOOSE.
15.8.3
Function block
BLOCK
IEC10000248 V1 EN-US
Figure 281: GOOSESPRCV function block
15.8.4
Signals
Table 486: GOOSESPRCV Input signals
Name
BLOCK
Table 487: GOOSESPRCV Output signals
Name
SPOUT
DATAVALID
COMMVALID
TEST
15.8.5
Settings
Table 488: GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
15.8.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
Line distance protection REL650
Technical manual
GOOSESPRCV
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
Type
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
0
Block of function
Description
Single point output
Data valid for single point output
Communication valid for single point output
Test output
Step
Default
-
Disabled
Station communication
GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v1
GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1
Description
Operation Off/On
GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v1
Section 15
PID-2527-INPUTSIGNALS v6
PID-2527-OUTPUTSIGNALS v6
PID-2527-SETTINGS v6
531