ABB Relion 650 Series Technical Manual page 432

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Monitoring
Set value
for
parameter
"Mode"
4
AB
5
BC
6
CA
7
A
8
B
9
C
* means complex conjugated value
It shall be noted that only in the first two operating modes that is, 1 & 2 the measurement function
calculates exact three-phase power. In other operating modes that is, from 3 to 9 it calculates the
three-phase power under assumption that the power system is fully symmetrical. Once the
complex apparent power is calculated then the P, Q, S, & PF are calculated in accordance with the
following formulas:
=
P
Re( )
EQUATION1403 V1 EN-US
426
Formula used for complex,
three-phase power calculation
(
=
×
*
-
S
V
I
AB
A
(Equation 66)
EQUATION1567 V1 EN-US
(
=
×
*
-
S
V
I
BC
B
(Equation 68)
EQUATION1569 V1 EN-US
(
=
×
-
*
S
V
I
CA
C
(Equation 70)
EQUATION1571 V1 EN-US
= ×
×
*
S
3
V I
A
A
(Equation 72)
EQUATION1573 V1 EN-US
= ×
×
*
S
3
V I
B
B
(Equation 74)
EQUATION1575 V1 EN-US
= ×
×
*
S
3
V I
C
C
(Equation 76)
EQUATION1577 V1 EN-US
S
© Copyright 2011 ABB Power Grids. All rights reserved
Formula used for voltage
and current magnitude
calculation
)
=
V
V
*
I
AB
B
(
=
+
I
I
A
EQUATION1568 V1 EN-US
)
=
V
V
*
I
BC
C
(
=
+
I
I
B
EQUATION1570 V1 EN-US
)
=
V
V
*
I
CA
A
(
=
+
I
I
C
EQUATION1572 V1 EN-US
=
×
V
3
V
=
I
I
A
EQUATION1574 V1 EN-US
=
×
V
3
V
=
I
I
B
EQUATION1576 V1 EN-US
=
×
V
3
V
=
I
I
C
EQUATION1578 V1 EN-US
Comment
Used when only V
phase voltage is available
)
I
/ 2
B
(Equation 67)
Used when only V
phase voltage is available
)
I
/ 2
C
(Equation 69)
Used when only V
phase voltage is available
)
I
/ 2
A
(Equation 71)
Used when only V
ground voltage is available
A
(Equation 73)
Used when only V
ground voltage is available
B
(Equation 75)
Used when only V
ground voltage is available
C
(Equation 77)
Line distance protection REL650
1MRK 506 326-UUS B
phase-to-
AB
phase-to-
BC
phase-to-
CA
phase-to-
A
phase-to-
B
phase-to-
C
(Equation 78)
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650