Section 10
Control
10.3.7
Technical data
Table 233: STBRREC (79) technical data
Function
Number of autoreclosing shots
Autoreclosing open time: Shot 1 - t1
3Ph
Shot 1 - t1 1Ph
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
Autorecloser maximum wait time
for sync
Open time extension for long trip
time
Maximum trip pulse duration
Inhibit reset time
Reset time
Minimum time CB must be closed
before AR becomes ready for
autoreclosing cycle
CB check time before unsuccessful
Wait for master release
Wait time after close command
before proceeding to next shot
10.4
Apparatus control
10.4.1
Functionality
The apparatus control functions are used for control and supervision of circuit breakers,
disconnectors and grounding switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchronism check, operator
place selection and external or internal blockings.
In normal security, the command is processed and the resulting position is not supervised.
However with enhanced security, the command is processed and the resulting position is
supervised.
314
Range or value
1-5
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
© Copyright 2011 ABB Power Grids. All rights reserved
1MRK 506 326-UUS B
GUID-232D44D3-1B89-4366-8F92-AFB2DD8BC477 v1
Accuracy
-
± 0.5% ± 25 ms
Line distance protection REL650
Technical manual