ABB Relion 650 Series Technical Manual page 592

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 17
IED physical connections
The events and setting values and all input data such as memorized values and disturbance
records can be read via the front communication port.
Only one of the possible clients can be used for parametrization at a time.
PCM600
LHMI
The default IP address of the IED through this port is 10.1.150.3.
The front port supports TCP/IP protocol. A standard Ethernet CAT 5 crossover cable is used with
the front port.
17.4.2
Station communication rear connection
The default IP address of the IED through the Ethernet connection is 192.168.1.10. The physical
connector is X1/LAN1. The interface speed is 100 Mbps for the 100BASE-FX LC alternative.
17.4.3
Optical serial rear connection
Serial communication can be used via optical connection in star topology. Connector type is either
glass (ST connector). Connection's idle state is indicated either with light on or light off. The
physical connector is X9/Rx,Tx.
17.4.4
Communication interfaces and protocols
Table 552: Supported station communication interfaces and protocols
Protocol
IEC 61850–8–1
DNP3
IEC 60870-5-103
● = Supported
17.4.5
Recommended industrial Ethernet switches
ABB recommends three third-party industrial Ethernet switches.
RuggedCom RS900
RuggedCom RS1600
RuggedCom RSG2100
586
Ethernet
100BASE-TX RJ-45
-
© Copyright 2011 ABB Power Grids. All rights reserved
Glass fibre (ST
100BASE-FX LC
connector)
-
1MRK 506 326-UUS B
GUID-46903990-A933-45C8-B277-5B8E4DB4297E v3
GUID-232BC617-0DBD-44A3-ACCB-D8B6DE044976 v1
GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v3
Serial
Plastic fibre (snap-in
connector)
-
-
-
-
GUID-41F05A0B-D39C-4BF7-829A-EB37C5D37CF4 v4
Line distance protection REL650
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents