Section 19
Technical data
19.3
Energizing inputs
Table 555: Energizing inputs
Description
Rated frequency
Operating range
Current inputs
Voltage inputs
1) Residual current
2) Phase currents or residual current
19.4
Binary inputs
Table 556: Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption/input
Threshold voltage
592
Rated current, I
n
Thermal withstand capability:
Continuously
For 1 s
For 10 s
Dynamic current withstand:
Half-wave value
Input impedance
Rated voltage, V
n
Voltage withstand:
Continuous
For 10 s
Burden at rated voltage
© Copyright 2011 ABB Power Grids. All rights reserved
Value
50/60 Hz
Rated frequency ± 5 Hz
1)
0.1/0.5 A
4 A
100 A
20 A
250 A
<100 mΩ
100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
420 V rms
450 V rms
<0.05 VA
Value
Maximum input voltage 300 V DC
24...250 V DC
1.6...1.8 mA
<0.3 W
15...221 V DC (parametrizable in the range in steps of 1% of
the rated voltage)
Line distance protection REL650
1MRK 506 326-UUS B
GUID-80AA04F6-C989-4E8A-81C0-1A9A7458ADCC v5
2)
1/5 A
20 A
500 A
100 A
1250 A
<20 mΩ
GUID-247871FB-80C1-4D7F-B860-9E98BBEC9E23 v2
Technical manual