ABB Relion 650 Series Technical Manual page 377

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Name
Values (Range)
OffDelay
0.000 - 60.000
ModeOutput1
Steady
Pulsed
ModeOutput2
Steady
Pulsed
ModeOutput3
Steady
Pulsed
12.3.6
Operation principle
Trip matrix logic (TMAGGIO) block is provided with 32 input signals and 3 output signals. The
function block incorporates internal logic OR gates in order to provide the necessary grouping of
connected input signals (for example, for tripping and alarming purposes) to the three output
signals from the function block.
Internal built-in OR logic is made in accordance with the following three rules:
1.
when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 (TRUE) the first
output signal (OUTPUT1) will get logical value 1 (TRUE).
2.
when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value 1 (TRUE) the
second output signal (OUTPUT2) will get logical value 1 (TRUE).
3.
when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 (TRUE) the third
output signal (OUTPUT3) will get logical value 1 (TRUE).
By use of the settings
OffDelay the behavior of each output can be customized. The OnDelay is always active and will
delay the input to output transition by the set time. The
decides wether the output shall be steady with an drop-off delay as set by
give a pulse with duration set by
connected in an OR-function a new pulse will only be given on the output if all related inputs are
reset and then one is activated again. And for steady operation the of delay will start when all
related inputs have reset. Detailed logical diagram is shown in figure
Line distance protection REL650
Technical manual
Unit
Step
s
0.001
-
-
-
-
-
-
ModeOutput1 , ModeOutput2 , ModeOutput3 , PulseTime , OnDelay and
PulseTime . Note that for pulsed operation since the inputs are
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
0.000
Output off delay time
Steady
Mode for output 1, steady or pulsed
Steady
Mode for output 2, steady or pulsed
Steady
Mode for output 3, steady or pulsed
ModeOutput for respective output
Section 12
SEMOD52537-5 v4
OffDelay or if it shall
204
Logic
371

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents