Section 6
Current protection
6.14.5
Settings
Table 140: BRCPTOC (46) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Pickup_ub
50 - 90
Pickup_PH
5 - 100
tOper
0.000 - 60.000
Table 141: BRCPTOC (46) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.14.6
Monitored data
Table 142: BRCPTOC (46) Monitored data
Name
IUNBAL
6.14.7
Operation principle
Broken conductor check (BRCPTOC, 46) detects a broken conductor condition by detecting the
asymmetry between currents in the three phases. The current-measuring elements continuously
measure the three-phase currents.
The current asymmetry signal output PICKUP is set on if:
The difference in currents between the phase with the lowest current and the phase with the
highest current is greater than set percentage
The lowest phase current is below 50% of the minimum setting value
The third condition is included to avoid problems in systems involving parallel lines. If a conductor
breaks in one phase on one line, the parallel line will experience an increase in current in the same
phase. This might result in the first two conditions being satisfied. If the unsymmetrical detection
lasts for a period longer than the set time
The simplified logic diagram of the broken conductor check function is shown in figure
BRCPTOC (46) is disabled (blocked) if:
218
Unit
Step
-
-
%IM
1
%IB
1
s
0.001
Unit
Step
-
1
Type
Values (Range)
REAL
-
tOper the TRIP output is activated.
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Disable / Enable
50
Unbalance current operation value in
percent of max current
20
Minimum phase current for operation of
pickup_ub> in % of Ibase
5.000
Operate time delay
Default
Description
1
Selection of one of the Global Base Value
groups
Unit
Description
-
Measured unbalance of phase currents
Pickup_ub of the highest phase current
1MRK 506 326-UUS B
PID-1123-SETTINGS v5
PID-1123-MONITOREDDATA v7
SEMOD171791-5 v4
Pickup_PH
116
Line distance protection REL650
Technical manual