ABB Relion 650 Series Technical Manual page 310

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
10.3.4
Signals
Table 229: STBRREC (79) Input signals
Name
ON
OFF
BLKON
BLKOFF
RESET
INHIBIT
PICKUP
TRSOTF
ZONESTEP
TR3P
THOLHOLD
CBREADY
52a
PLCLOST
SYNC
WAIT
RSTCOUNT
Table 230: STBRREC (79) Output signals
Name
BLOCKED
SETON
READY
ACTIVE
SUCCL
UNSUCCL
INPROGR
1PT1
3PT1
3PT2
3PT3
3PT4
3PT5
PREP3P
Table continues on next page
304
Type
Default
Description
BOOLEAN
0
Enables AR when Operation = ExternalCtrl
BOOLEAN
0
Disables AR when Operation = ExternalCtrl
BOOLEAN
0
Sets AR in blocked state
BOOLEAN
0
Releases AR from blocked state
BOOLEAN
0
Resets AR to initial conditions
BOOLEAN
0
Interrupts and inhibits reclosing sequence
BOOLEAN
0
Reclosing sequence starts by a protection trip signal
BOOLEAN
0
Makes AR to continue to shots 2-5 at a trip from SOTF
BOOLEAN
0
Coordination between local AR and down stream devices
BOOLEAN
1
Signal to AR that a three-phase tripping occurred
BOOLEAN
0
Holds AR in wait state
BOOLEAN
0
CB must be ready for CO/OCO operation to allow start / close
BOOLEAN
0
Status of the circuit breaker Closed/Open
BOOLEAN
0
Power line carrier or other form of permissive signal lost
BOOLEAN
0
Synchronizing check fulfilled for 3Ph closing attempts
BOOLEAN
0
Wait for master in Multi-breaker arrangements
BOOLEAN
0
Resets all counters
Type
Description
BOOLEAN
Wait for master in Multi-breaker arrangements
BOOLEAN
AR operation is switched on
BOOLEAN
Indicates that AR is ready for a new sequence
BOOLEAN
Reclosing sequence in progress
BOOLEAN
Activated if CB closes during the time tUnsucCl
BOOLEAN
Reclosing unsuccessful, signal resets after the reclaim time
BOOLEAN
Reclosing shot in progress, activated during open reset
BOOLEAN
Single-phase reclosing in progress, shot 1
BOOLEAN
Three-phase reclosing in progress, shot 1
BOOLEAN
Three-phase reclosing in progress, shot 2
BOOLEAN
Three-phase reclosing in progress, shot 3
BOOLEAN
Three-phase reclosing in progress, shot 4
BOOLEAN
Three-phase reclosing in progress, shot 5
BOOLEAN
Prepare three-pole trip, control of the next trip operation
© Copyright 2011 ABB Power Grids. All rights reserved
1MRK 506 326-UUS B
PID-2350-INPUTSIGNALS v7
PID-2350-OUTPUTSIGNALS v7
Line distance protection REL650
Technical manual