Section 13
Monitoring
13.1.6
Operation principle
Upon receiving a signal at its input, IEC61850 generic communication I/O functions (SPGGIO)
function sends the signal over IEC 61850-8-1 to the equipment or system that requests this signal.
To get the signal, PCM600 must be used to define which function block in which equipment or
system should receive this information.
13.2
IEC 61850 generic communication I/O functions 16
inputs SP16GGIO
13.2.1
Identification
Function description
IEC 61850 generic communication
I/O functions 16 inputs
13.2.2
Functionality
IEC 61850 generic communication I/O functions 16 inputs (SP16GGIO) function is used to send up
to 16 logical signals to other systems or equipment in the substation.
13.2.3
Function block
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC09000238 V1 EN-US
Figure 222: SP16GGIO function block
398
SP16GGIO
IEC09000238_en_1.vsd
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
SP16GGIO
-
1MRK 506 326-UUS B
GUID-856A4830-FFB4-40CE-9619-E42A74DFEF88 v1
ANSI/IEEE C37.2
device number
-
GUID-57C173AB-E8FA-4E97-BA86-9A5588E0619B v1
GUID-EEB6E300-E0AA-4603-A929-5ACC930599C8 v1
Line distance protection REL650
Technical manual