ABB Relion 650 Series Technical Manual page 213

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
6.11.5
Settings
Table 121: CSPRBRF (50BF) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
FunctionMode
Current
Contact
Current&Contact
BuTripMode
2 out of 4
1 out of 3
1 out of 4
RetripMode
Retrip Off
CB Pos Check
No CBPos Check
Pickup_PH
5 - 200
Pickup_N
2 - 200
t1
0.000 - 60.000
t2
0.000 - 60.000
t2MPh
0.000 - 60.000
Table 122: CSPRBRF (50BF) Group settings (advanced)
Name
Values (Range)
Pickup_BlkCont
5 - 200
Table 123: CSPRBRF (50BF) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.11.6
Monitored data
Table 124: CSPRBRF (50BF) Monitored data
Name
IA
IB
IC
IN
Line distance protection REL650
Technical manual
Unit
Step
-
-
-
-
-
-
-
-
%IB
1
%IB
1
s
0.001
s
0.001
s
0.001
Unit
Step
%IB
1
Unit
Step
-
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Disable / Enable
Current
Detection principle for back-up trip
1 out of 3
Back-up trip mode
Retrip Off
Operation mode of re-trip logic
10
Phase current pickup in % of IBase
10
Operate residual current level in % of IBase
0.000
Time delay of re-trip
0.150
Time delay of back-up trip
60.000
Time delay of back-up trip at multi-phase
pickup
Default
Description
20
Current for blocking of 52a operation in %
of Ibase
Default
Description
1
Selection of one of the Global Base Value
groups
Unit
Description
A
Measured current in phase A
A
Measured current in phase B
A
Measured current in phase C
A
Measured residual current
Section 6
Current protection
PID-2349-SETTINGS v7
PID-2349-MONITOREDDATA v7
207

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents