ABB Relion 650 Series Technical Manual page 597

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Section 19
19.1
Dimensions
Table 553: Dimensions of the IED - half 19" rack
Description
Width
Height
Depth
Weight box
Weight LHMI
19.2
Power supply
Table 554: Power supply
Description
V
n
V
variation
n
Maximum load of auxiliary voltage
supply
Ripple in the DC auxiliary voltage
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
Line distance protection REL650
Technical manual
Technical data
600PSM02
100, 110, 120, 220, 240 V AC, 50 and
60 Hz
110, 125, 220, 250 V DC
85...110% of V
80...120% of V
35 W
Max 15% of the DC value (at frequency of 100 Hz)
50 ms at V
© Copyright 2011 ABB Power Grids. All rights reserved
Value
8.66 inches (220 mm)
10.47 inches (265.9 mm), 6U
9.82 inches (249.5 mm)
<22.04 lbs (10 kg), 6U
2.87 lbs (1.3 kg), 6U
600PSM03
48, 60, 110, 125 V DC
(85...264 V AC)
80...120% of V
n
(88...300 V DC)
n
n
Section 19
Technical data
GUID-33B28FB3-7FCF-4DEC-A194-C79D725805D6 v5
GUID-B8B53053-FE79-47B1-AEDB-904B91B54175 v4
(38.4...150 V DC)
n
591

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650