Section 5
Impedance protection
ANSI09000120 V1 EN-US
Figure 62: Simplified offset mho characteristic and vector diagram for phase A-to-ground
Operation occurs if 90≤β≤270.
Offset mho
The characteristic for offset mho at ground fault is a circle containing the two vectors from the
Z and ZRev where Z and Zrev are the setting reach for the positive sequence impedance in
origin
forward, reverse direction respectively. The vector
LineAng and the angle for ZRev is LineAng +180°.
The condition for operation at phase-to-ground fault is that the angle β between the two
compensated voltages Vcomp1 and Vcomp2 is greater or equal to 90° see figure 63. The angle will
be 90° for fault location on the boundary of the circle.
The angle β for A-to-ground fault can be defined as
β =
arg
EQUATION1802-ANSI-650 V1 EN-US
Table continues on next page
114
I
X
I
·Z
A
fault
V
I Z
A
A
(
)
− −
V
I Z
Re
v
A
A
© Copyright 2011 ABB Power Grids. All rights reserved
I
·ZN
A
V
comp
ß
I
Z
A
loop
Vpol
f
I
( Ref)
A
ANSI09000120-1-en.vsd
Z in the impedance plane has the settable angle
1MRK 506 326-UUS B
I
·R
A
Line distance protection REL650
Technical manual
SEMOD154224-309 v4
(Equation 20)