ABB Relion 650 Series Technical Manual page 188

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Current protection
6.7.2
Functionality
In isolated networks or in networks with high impedance grounding, the ground fault current is
significantly smaller than the short circuit currents. In addition to this, the magnitude of the fault
current is almost independent on the fault location in the network. The protection can be selected
to use either the residual current or residual power component 3V
quantity. There is also available one non-directional 3I
overvoltage tripping step.
6.7.3
Function block
I3P*
V3P*
BLOCK
BLKVN
ANSI08000036 V1 EN-US
Figure 95: SDEPSDE (67N) function block
6.7.4
Signals
Table 95: SDEPSDE (67N) Input signals
Name
I3P
V3P
BLOCK
BLKVN
Table 96: SDEPSDE (67N) Output signals
Name
TRIP
TRDIRIN
TRNDIN
TRVN
PICKUP
PUDIRIN
Table continues on next page
182
SDEPSDE (67N)
TRIP
TRDIRIN
TRNDIN
TRVN
PICKUP
PUDIRIN
PUNDIN
PUVN
PUFW
PUREV
CND
VNREL
ANSI08000036-1-en.vsd
Type
GROUP
SIGNAL
GROUP
SIGNAL
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
step and one non-directional 3V
0
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Blocks the non-directional voltage residual outputs
Description
Common trip signal
Trip of the directional residual overcurrent
Trip of non-directional residual overcurrent
Trip of non-directional residual overvoltage
General pickup signal
Pick up of the directional residual overcurrent function
1MRK 506 326-UUS B
GUID-EB27F20E-F477-418B-83F0-744BF2988469 v2
·3I
·cos j, for operating
0
0
0
PID-1975-INPUTSIGNALS v6
PID-1975-OUTPUTSIGNALS v5
Line distance protection REL650
Technical manual
SEMOD172780-4 v4