1MRK 506 326-UUS B
7.3.8
Technical data
Table 181: ROV2PTOV (59N) technical data
Function
Operate voltage, step 1
Operate voltage, step 2
Reset ratio
Inverse time characteristics for low
and high step, see table
Definite time setting, step 1
Definite time setting, step 2
Minimum operate time for step 1
inverse characteristic
Operate time, pickup function
Reset time, pickup function
Critical impulse time
Impulse margin time
7.4
Loss of voltage check LOVPTUV (27)
7.4.1
Identification
Function description
Loss of voltage check
7.4.2
Functionality
Loss of voltage check (LOVPTUV, 27) is suitable for use in networks with an automatic system
restoration function. LOVPTUV (27) issues a three-pole trip command to the circuit breaker, if all
three phase voltages fall below the set value for a time longer than the set time and the circuit
breaker remains closed.
Line distance protection REL650
Technical manual
Range or value
(1-200)% of
(1–100)% of
>95%
-
578
(0.00–6000.00) s
(0.000–60.000) s
(0.000-60.000) s
30 ms typically at 0 to 2 x V
40 ms typically at 2 to 0 x V
10 ms typically at 0 to 2 x V
15 ms typically
IEC 61850
identification
LOVPTUV
© Copyright 2011 ABB Power Grids. All rights reserved
VBase
VBase
set
set
set
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
27
Section 7
Voltage protection
M13317-2 v5
Accuracy
± 0.5% of V
at V < V
n
n
± 0.5% of V at V > V
n
± 0.5% of V
at V < V
n
n
± 0.5% of V at V > V
n
-
See table
578
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms
-
-
-
-
SEMOD171453-1 v3
SEMOD171954-2 v2
SEMOD171457-5 v4
251