1MRK 506 326-UUS B
Name
VB1OK
VB1FF
VB2OK
VB2FF
VLNOK
VLNFF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
Table 219: SESRSYN (25) Output signals
Name
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
VSELFAIL
B1SEL
B2SEL
LNSEL
SYNPROGR
SYNFAIL
FRDIFSYN
FRDERIVA
VOKSC
VDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
Table continues on next page
Line distance protection REL650
Technical manual
Type
Default
Description
BOOLEAN
0
Bus1 voltage transformer OK
BOOLEAN
0
Bus1 voltage transformer fuse failure
BOOLEAN
0
Bus2 voltage transformer OK
BOOLEAN
0
Bus2 voltage transformer fuse failure
BOOLEAN
0
Line voltage transformer OK
BOOLEAN
0
Line voltage transformer fuse failure
BOOLEAN
0
Start synchronizing
BOOLEAN
0
Set synchronizing in test mode
BOOLEAN
0
Set synchro check in test mode
BOOLEAN
0
Set energizing check in test mode
INTEGER
0
Input for setting of automatic energizing mode
INTEGER
0
Input for setting of manual energizing mode
Type
Description
BOOLEAN
Synchronizing OK output
BOOLEAN
Auto synchronism-check OK
BOOLEAN
Automatic energizing check OK
BOOLEAN
Manual synchronism-check OK
BOOLEAN
Manual energizing check OK
BOOLEAN
Synchronizing OK test output
BOOLEAN
Auto synchronism-check OK test output
BOOLEAN
Manual synchronism-check OK test output
BOOLEAN
Energizing check OK test output
BOOLEAN
Selected voltage transformer fuse failed
BOOLEAN
Bus1 selected
BOOLEAN
Bus2 selected
BOOLEAN
Line selected
BOOLEAN
Synchronizing in progress
BOOLEAN
Synchronizing failed
BOOLEAN
Frequency difference out of limit for synchronizing
BOOLEAN
Frequency derivative out of limit for synchronizing
BOOLEAN
Voltage amplitudes above set limits
BOOLEAN
Voltage difference out of limit
BOOLEAN
Frequency difference out of limit for Auto operation
BOOLEAN
Phase angle difference out of limit for Auto operation
BOOLEAN
Frequency difference out of limit for Manual operation
BOOLEAN
Phase angle difference out of limit for Manual Operation
© Copyright 2011 ABB Power Grids. All rights reserved
Section 10
Control
PID-2594-OUTPUTSIGNALS v6
285