1MRK 506 326-UUS B
Table 360: CVMMXN Non group settings (advanced)
Name
Values (Range)
SDbRepInt
1 - 300
SZeroDb
0 - 100000
SHiHiLim
0.0 - 2000.0
SHiLim
0.0 - 2000.0
PHiHiLim
-2000.0 - 2000.0
SLimHyst
0.000 - 100.000
PDbRepInt
1 - 300
PZeroDb
0 - 100000
PHiLim
-2000.0 - 2000.0
PLowLim
-2000.0 - 2000.0
PLowLowLim
-2000.0 - 2000.0
PLimHyst
0.000 - 100.000
QDbRepInt
1 - 300
QZeroDb
0 - 100000
QHiHiLim
-2000.0 - 2000.0
QHiLim
-2000.0 - 2000.0
QLowLim
-2000.0 - 2000.0
QLowLowLim
-2000.0 - 2000.0
QLimHyst
0.000 - 100.000
PFDbRepInt
1 - 300
PFZeroDb
0 - 100000
PFHiHiLim
-1.000 - 1.000
PFHiLim
-1.000 - 1.000
PFLowLim
-1.000 - 1.000
PFLowLowLim
-1.000 - 1.000
PFLimHyst
0.000 - 100.000
VDbRepInt
1 - 300
VZeroDb
0 - 100000
VHiHiLim
0.0 - 200.0
VHiLim
0.0 - 200.0
VLowLim
0.0 - 200.0
VLowLowLim
0.0 - 200.0
Table continues on next page
Line distance protection REL650
Technical manual
Unit
Step
Type
1
m%
1
%SB
0.1
%SB
0.1
%SB
0.1
%
0.001
Type
1
m%
1
%SB
0.1
%SB
0.1
%SB
0.1
%
0.001
Type
1
m%
1
%SB
0.1
%SB
0.1
%SB
0.1
%SB
0.1
%
0.001
Type
1
m%
1
-
0.001
-
0.001
-
0.001
-
0.001
%
0.001
Type
1
m%
1
%VB
0.1
%VB
0.1
%VB
0.1
%VB
0.1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping in 0.001% of range
150.0
High High limit in % of SBase
120.0
High limit in % of SBase
150.0
High High limit in % of SBase
5.000
Hysteresis value in % of range (common
for all limits)
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping
120.0
High limit in % of SBase
-120.0
Low limit in % of SBase
-150.0
Low Low limit in % of SBase
5.000
Hysteresis value in % of range (common
for all limits)
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping
150.0
High High limit in % of SBase
120.0
High limit in % of SBase
-120.0
Low limit in % of SBase
-150.0
Low Low limit in % of SBase
5.000
Hysteresis value in % of range (common
for all limits)
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping
1.000
High High limit (physical value)
0.800
High limit (physical value)
-0.800
Low limit (physical value)
-1.000
Low Low limit (physical value)
5.000
Hysteresis value in % of range (common
for all limits)
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping
150.0
High High limit in % of UBase
120.0
High limit in % of UBase
80.0
Low limit in % of UBase
60.0
Low Low limit in % of UBase
Section 13
Monitoring
407

Advertisement