ABB Relion 650 Series Technical Manual page 89

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
5.1.7
Technical data
Table 19:
Function
Number of zones
Minimum operate residual
current
Minimum operate current,
phase-to-phase and phase-to-
ground
Positive sequence impedance
reach for zones
Fault resistance, phase-to-
ground
Fault resistance, phase-to-
phase
Line angle for zones
Magnitude of ground return
compensation factor KN for
zones
Angle for groundreturn
compensation factor KN for
zones
Dynamic overreach
Impedance zone timers
Operate time
Reset ratio
Reset time
5.2
Phase selection with load encroachment, quadrilateral
characteristic FDPSPDIS (21)
5.2.1
Identification
Function description
Phase selection with load
encroachment, quadrilateral
characteristic
Line distance protection REL650
Technical manual
ZQDPDIS (21) Technical data
Range or value
5 with selectable
direction
(5-30)% of IBase
(10-30)% of IBase
0.005 - 3000.000
(1.00-9000.00) Ω/
loop
(1.00-3000.00) Ω/
loop
(0 - 180) degrees
0.00 - 3.00
(-180 - 180) degrees
<5% at 85 degrees
measured with
CVT's and
0.5<SIR<30
(0.000-60.000) s
30 ms typically
105% typically
35 ms typically
© Copyright 2011 ABB Power Grids. All rights reserved
Accuracy
-
± 1,0 % of I
± 1,0 % of I
± 5.0% static accuracy
± 2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x V
Current range: (0.5-30) x I
Angle: at 0 degrees and 85 degrees
-
-
-
± 0.5% ± 10 ms
-
-
-
IEC 61850
IEC 60617
identification
identification
FDPSPDIS
Z<phs
SYMBOL-DD V1 EN-US
Impedance protection
n
n
n
n
GUID-F265B933-B626-41CD-89BA-C6710C5DA78A v1
ANSI/IEEE C37.2
device number
21
Section 5
M13842-1 v8
M14850-1 v5
83