Section 13
Monitoring
Name
SET_P_LO
SET_T_LO
RESET_LO
Table 429: SSIMG (63) Output signals
Name
PRESSURE
PRES_ALM
PRES_LO
TEMP
TEMP_ALM
TEMP_LO
13.15.5
Settings
Table 430: SSIMG (63) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PressAlmLimit
0.00 - 25.00
PressLOLimit
0.00 - 25.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tPressureAlarm
0.000 - 60.000
tPressureLO
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetPressAlm
0.000 - 60.000
tResetPressLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
tResetTempLO
0.000 - 60.000
13.15.6
Operation principle
Insulation gas monitoring function SSIMG (63) is used to monitor gas pressure in the circuit
breaker. Two binary output signals are used from the circuit breaker to initiate alarm signals,
pressure below alarm level and pressure below lockout level. If the input signal PRES_ALM is high,
484
Type
Default
Description
BOOLEAN
0
Set pressure lockout
BOOLEAN
0
Set temperature lockout
BOOLEAN
0
Reset pressure and temperature lockout
Type
Description
REAL
Pressure service value
BOOLEAN
Pressure below alarm level
BOOLEAN
Pressure below lockout level
REAL
Temperature of the insulation medium
BOOLEAN
Temperature above alarm level
BOOLEAN
Temperature above lockout level
Unit
Step
-
-
-
0.01
-
0.01
-
0.01
-
0.01
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
5.00
Alarm setting for pressure
3.00
Pressure lockout setting
30.00
Temperature alarm level setting of the
medium
30.00
Temperature lockout level of the medium
0.000
Time delay for pressure alarm
0.000
Time delay for pressure lockout indication
0.000
Time delay for temperature alarm
0.000
Time delay for temperture lockout
0.000
Reset time delay for pressure alarm
0.000
Reset time delay for pressure lockout
0.000
Reset time delay for temperture alarm
0.000
Reset time delay for temperture lockout
1MRK 506 326-UUS B
PID-1840-OUTPUTSIGNALS v5
PID-1840-SETTINGS v5
GUID-359458EA-FFAA-4A44-A8E8-9469CA069C80 v2
Line distance protection REL650
Technical manual