10.3.6.11
Initiation of reclosing from CB open information
If a user wants to apply initiation of auto-reclosing from CB open position instead of from
protection trip signals, the function offers such a possibility. This starting mode is selected by a
setting parameter
operations. Typically, one also set
contact of type NC (normally closed) to inputs 52a and RI. When the signal changes from CB closed
to CB open an auto-reclosing start pulse of limited length is generated and latched in the function,
subject to the usual checks. Then the reclosing sequence continues as usual. One needs to connect
signals from manual tripping and other functions, which shall prevent reclosing, to the input
INHIBIT.
StartByCBOpen= Enabled
RI
RI_HS
ANSI10000262 V1 EN-US
Figure 164: Pulsing of the start inputs
Line distance protection REL650
Technical manual
StartByCBOpen = Enabled . One needs then to block reclosing at all manual trip
CBAuxContType = NormClosed and connect a CB auxiliary
NOT
AND
AND
AND
AND
© Copyright 2011 ABB Power Grids. All rights reserved
PICKUP
³1
100 ms
100 ms
ANSI10000262-1-en.vsd
Section 10
Control