ABB Relion 650 Series Technical Manual page 330

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
10.5.6
Monitored data
Table 246: SLGGIO Monitored data
Name
SWPOSN
10.5.7
Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGGIO) function has two
operating inputs – UP and DOWN. When a signal is received on the UP input, the block will activate
the output next to the present activated output, in ascending order (if the present activated
output is 3 – for example and one operates the UP input, then the output 4 will be activated). When
a signal is received on the DOWN input, the block will activate the output next to the present
activated output, in descending order (if the present activated output is 3 – for example and one
operates the DOWN input, then the output 2 will be activated). Depending on the output settings
the output signals can be steady or pulsed. In case of steady signals, in case of UP or DOWN
operation, the previously active output will be deactivated. Also, depending on the settings one
can have a time delay between the UP or DOWN activation signal positive front and the output
activation.
Besides the inputs visible in the application configuration in the Application Configuration tool,
there are other possibilities that will allow an user to set the desired position directly (without
activating the intermediate positions), either locally or remotely, using a "select before execute"
dialog. One can block the function operation, by activating the BLOCK input. In this case, the
present position will be kept and further operation will be blocked. The operator place (local or
remote) is specified through the PSTO input. If any operation is allowed the signal INTONE from
the Fixed signal function block can be connected. SLGGIO function block has also an integer value
output, that generates the actual position number. The positions and the block names are fully
settable by the user. These names will appear in the menu, so the user can see the position names
instead of a number.
10.6
Selector mini switch VSGGIO
10.6.1
Identification
Function description
Selector mini switch
10.6.2
Functionality
The Selector mini switch VSGGIO function block is a multipurpose function used for a variety of
applications, as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol on the single line diagram (SLD) on the
local HMI.
324
Type
Values (Range)
INTEGER
-
IEC 61850
identification
VSGGIO
© Copyright 2011 ABB Power Grids. All rights reserved
Unit
Description
-
Switch position as integer value
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Line distance protection REL650
1MRK 506 326-UUS B
PID-1868-MONITOREDDATA v8
SEMOD114931-4 v5
SEMOD167850-2 v2
SEMOD158756-5 v5
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents