1MRK 506 326-UUS B
Table 313: INVERTER Output signals
Name
OUT
Settings
The function does not have any parameters available in Local HMI or Protection and Control IED
Manager (PCM600).
12.4.1.4
PULSETIMER function block
Identification
Function description
PULSETIMER function block
Functionality
The pulse function can be used, for example for pulse extensions or limiting of operation of
outputs. The PULSETIMER has a settable length.
Function block
INPUT
IEC09000291 V1 EN-US
Figure 207: PULSETIMER function block
Signals
Table 314: PULSETIMER Input signals
Name
INPUT
Table 315: PULSETIMER Output signals
Name
OUT
Settings
Table 316: PULSETIMER Non group settings (basic)
Name
Values (Range)
t
0.000 -
90000.000
Line distance protection REL650
Technical manual
Type
BOOLEAN
PULSETIMER
OUT
IEC09000291-1-en.vsd
Type
Default
BOOLEAN
0
Type
BOOLEAN
Unit
s
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Output signal
IEC 61850
IEC 60617
identification
identification
PULSETIMER
-
Description
Input signal
Description
Output signal
Step
Default
0.001
0.010
GUID-50A2CEA0-2781-4C5F-B184-F09FC666876F v1
GUID-2109B7AF-2BF1-4327-82F3-44754C066F0F v1
ANSI/IEEE C37.2
device number
-
GUID-7A08F2DE-B6F3-456E-AB0C-F68B05C7AF90 v1
GUID-9690C813-36BE-4C35-B7B1-D52ACEA00AB4 v2
Description
Pulse time length
Section 12
Logic
PID-1815-OUTPUTSIGNALS v7
PID-1820-INPUTSIGNALS v7
PID-1820-OUTPUTSIGNALS v7
PID-1820-SETTINGS v7