ABB Relion 650 Series Technical Manual page 278

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 9
Secondary system supervision
Name
52a
MCBOP
89b
Table 209: SDDRFUF Output signals
Name
BLKZ
BLKV
3PH
DLD1PH
DLD3PH
9.2.5
Settings
Table 210: SDDRFUF Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
3V0PU
1 - 100
3I0PU
1 - 100
3V2PU
1 - 100
3I2PU
1 - 100
OpDVDI
Disabled
Enabled
DVPU
1 - 100
DIPU
1 - 100
VPPU
1 - 100
50P
1 - 100
SealIn
Disabled
Enabled
Table continues on next page
272
Type
Default
Description
BOOLEAN
0
Active when circuit breaker is closed
BOOLEAN
0
Active when external Miniature Circuit Breaker opens protected
voltage circuit
BOOLEAN
0
Active when line disconnect switch is open
Type
Description
BOOLEAN
Start of current and voltage controlled function
BOOLEAN
General pickup
BOOLEAN
Three-phase pickup
BOOLEAN
Dead line condition in at least one phase
BOOLEAN
Dead line condition in all three phases
Unit
Step
-
-
-
-
%VB
1
%IB
1
%VB
1
%IB
1
-
-
%VB
1
%IB
1
%VB
1
%IB
1
-
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Enabled
Disable/Enable Operation
V0I0
Operating mode selection
30
Pickup of residual overvoltage element in
% of VBase
10
Pickup of residual undercurrent element in
% of IBase
30
Pickup of negative sequence overvoltage
element in % of VBase
10
Pickup of negative sequence undercurrent
element in % of IBase
Disabled
Operation of change based function
Disable/Enable
60
Pickup of change in phase voltage in % of
VBase
15
Pickup of change in phase current in % of
IBase
70
Pickup of phase voltage in % of VBase
10
Pickup of phase current in % of IBase
Enabled
Seal in functionality Disable/Enable
1MRK 506 326-UUS B