Section 5
Impedance protection
5.2.2
Functionality
The operation of transmission networks today is in many cases close to the stability limit. Due to
environmental considerations, the rate of expansion and reinforcement of the power system is
reduced, for example, difficulties to get permission to build new power lines. Phase selection,
quadrilateral characteristic with fixed angle FDPSPDIS (21) is designed to accurately select the
proper faulted loop(s) in the distance function based on the fault type.
The heavy load transfer that is common in many transmission networks may make fault resistance
coverage difficult to achieve. Therefore, FDPSPDIS (21) has a built-in algorithm for load
encroachment, which gives the possibility to enlarge the resistive setting of both the phase
selection and the measuring zones without interfering with the load.
The extensive output signals from the phase selection gives also important information about
faulty phase(s), which can be used for fault analysis.
5.2.3
Function block
I3P*
V3P*
BLOCK
DIRCND
ANSI09000061 V1 EN-US
Figure 40: FDPSPDIS (21) function block
5.2.4
Signals
Table 20: FDPSPDIS Input signals
Name
I3P
V3P
BLOCK
DIRCND
84
FDPSPDIS
TRIP
PICKUP
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
NDIR_A
NDIR_B
NDIR_C
NDIR_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
STCNDZI
DLECND
ANSI09000061-1-en.vsd
Type
Default
GROUP
-
SIGNAL
GROUP
-
SIGNAL
BOOLEAN
0
INTEGER
0
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Three phase group signal for current inputs
Three phase group signal for voltage inputs
Block of function
External directional condition
1MRK 506 326-UUS B
M13139-3 v6
M13147-3 v4
PID-1538-INPUTSIGNALS v6
Line distance protection REL650
Technical manual