ABB Relion 650 Series Technical Manual page 200

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Current protection
6.8.4
Signals
Table 101: UC2PTUC (37) Input signals
Name
I3P
BLOCK
BLK1
BLK2
Table 102: UC2PTUC (37) Output signals
Name
TRIP
TRST1
TRST2
RI
PU_ST1
PU_ST2
6.8.5
Settings
Table 103: UC2PTUC (37) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
I1Mode
1 out of 3
2 out of 3
3 out of 3
I1<
5.0 - 100.0
t1
0.000 - 60.000
tReset1
0.000 - 60.000
I2Mode
1 out of 3
2 out of 3
3 out of 3
I2<
5.0 - 100.0
t2
0.000 - 60.000
tReset2
0.000 - 60.000
tPulse
0.01 - 2.00
IBlk
5.0 - 100.0
194
Type
Default
Description
GROUP
-
Three phase group signal for current input
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of step 1
BOOLEAN
0
Block of step 2
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Trip signal for step 1
BOOLEAN
Trip signal for step 2
BOOLEAN
General pickup signal
BOOLEAN
Start of step 1
BOOLEAN
Start of step 2
Unit
Step
-
-
-
-
%IB
1.0
s
0.001
s
0.001
-
-
%IB
1.0
s
0.001
s
0.001
s
0.01
%IB
1.0
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Disable / Enable
1 out of 3
Number of phases required to operate for
step 1
10.0
Current setting for step 1 in % of IBase
5.000
Time delay for step 1
0.000
Reset time delay for step 1
1 out of 3
Number of phases required to operate for
step 2
30.0
Current setting for step 2 in % of IBase
2.000
Time delay for step 2
0.000
Reset time delay for step 2
0.10
Operate pulse duration
5.0
Current setting for blocking in % of IBase
1MRK 506 326-UUS B
PID-1522-INPUTSIGNALS v6
PID-1522-OUTPUTSIGNALS v6
PID-1522-SETTINGS v6
Line distance protection REL650
Technical manual