ABB Relion 650 Series Technical Manual page 374

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Logic
BLOCK
INTL_ATRIP
INTL_BTRIP
INTL_CTRIP
ABC_TRIP
ANSI10000269 V1 EN-US
Figure 202: Final tripping circuits
12.2.7
Technical data
Table 306: SPTPTRC (94) technical data
Function
Trip action
Timers
12.3
Trip matrix logic TMAGGIO
12.3.1
Identification
Function description
Trip matrix logic
12.3.2
Functionality
Trip matrix logic TMAGGIO function is used to route trip signals and other logical output signals to
different output contacts on the IED.
368
AND
OR
AND
OR
AND
OR
OR
AND
AND
AND
AND
Range or value
3-Ph, 1/3-Ph
(0.000-60.000) s
IEC 61850
identification
TMAGGIO
© Copyright 2011 ABB Power Grids. All rights reserved
AND
OR
-loop
10 ms
AND
5 ms
AND
OR
-loop
IEC 60617
identification
-
1MRK 506 326-UUS B
TR_A
TR_B
TR_C
TRIP
TR3P
TR1P
0
TR2P
0
ANSI10000269-1-en.vsd
GUID-19FB0445-FD04-4CF8-AF88-9B9BC823F052 v1
Accuracy
-
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
-
Line distance protection REL650
Technical manual
SEMOD167882-2 v2