ABB Relion 650 Series Technical Manual page 110

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 5
Impedance protection
Name
Values (Range)
OpModeLG2
Disabled
Enabled
tLG2
0.000 - 60.000
OpModetPP2
Disabled
Enabled
tPP2
0.000 - 60.000
OpModeLG3
Disabled
Enabled
tLG3
0.000 - 60.000
OpModetPP3
Disabled
Enabled
tPP3
0.000 - 60.000
OpModeLG4
Disabled
Enabled
tLG4
0.000 - 60.000
OpModetPP4
Disabled
Enabled
tPP4
0.000 - 60.000
OpModeLG5
Disabled
Enabled
tLG5
OpModetPP5
tPP5
OpMode1
OpMode2
Z1Rev
Z1
Z2
Z2Rev
Table continues on next page
104
Unit
-
s
-
s
-
s
-
s
-
s
-
s
-
0.000 - 60.000
s
Disabled
-
Enabled
0.000 - 60.000
s
Disable-Zone
-
enable-PhG
enable-PhPh
enable PhG PhPh
Disable-Zone
-
enable-PhG
enable-PhPh
enable PhG PhPh
0.005 - 3000.000
ohm/p
0.005 - 3000.000
ohm/p
0.005 - 3000.000
ohm/p
0.005 - 3000.000
ohm/p
© Copyright 2011 ABB Power Grids. All rights reserved
Step
Default
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
-
enable PhG PhPh
-
enable PhG PhPh
0.001
30.000
0.001
30.000
0.001
30.000
0.001
30.000
1MRK 506 326-UUS B
Description
Operation mode Off / On of zone timer,
Phase-ground for zone 2
Time delay to trip of Phase-ground
elements for zone 2
Operation mode Off / On of zone timer,
Phase-Phase for zone 2
Time delay to trip of Phase-Phase
elements for zone 2
Operation mode Off / On of zone timer,
Phase-ground for zone 3
Time delay to trip of Phase-ground
lements for zone 3
Operation mode Off / On of zone timer,
Phase-Phase for zone 3
Time delay to trip of Phase-Phase
elements for zone 3
Operation mode Off / On of zone timer,
Phase-ground for zone 4
Time delay to trip of Phase- Ground
elements for zone 4
Operation mode Off / On of zone timer,
Phase-Phase for zone 4
Time delay to trip of Phase-Phase
elements for zone 4
Operation mode Off / On of zone timer,
Phase-Ground for zone 5
Time delay to trip of Phase- Ground
elements for zone 5
Operation mode Off / On of zone timer,
Phase-Phase for zone 5
Time delay to trip of Phase-Phase
elements for zone 5
Operation mode of zone 1
Operation mode of zone 2
Reverse positive sequence impedance
setting for zone 1
Positive sequence impedance setting for
zone 1
Positive sequence impedance setting for
zone 2
Reverse positive sequence impedance
setting for zone 2
Line distance protection REL650
Technical manual