ABB Relion 650 Series Technical Manual page 314

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
1PT1
3PT1TO
3PT2TO
3PT3TO
3PT4TO
3PT5TO
SYNC
initiate
CBREADY
Pulse STBRREC (79) (above)
TR3P
pickup
initiate
Shot 0
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5
INHIBIT
ANSI10000256 V2 EN-US
Figure 158: Auto-reclosing Disabled/Enabled and start
10.3.6.3
Auto-reclosing mode selection
The Auto-reclosing mode is selected with setting
+1*3ph (4) .
The following integers shall be used.
10.3.6.4
Control of the auto-reclosing open time for shot 1
Up to four different time settings can be used for the first shot, and one extension time. There are
separate settings for single- and three-phase auto-reclosing open time,
particular input signal is applied, and an autoreclosing program with single-phase reclosing is
selected, the auto-reclosing open time
connection with start, the auto-reclosing open time for three-phase reclosing is used.
308
OR
AND
AND
AND
LOGIC
reclosing
programs
Blocking out
OR
© Copyright 2011 ABB Power Grids. All rights reserved
"STBRREC (79) Open time"
From logic for
t1 3Ph
reclosing
t
programs
AND
AND
tSync
t
tReset
AND
t
OR
Reset Timer On
1PT1
3PT1
OR
3PT2
3PT3
3PT4
3PT5
tInhibit
Inhibit (internal)
t
ARMode = 3 phase (0) , 1/3ph (1) , 1ph (2) , 1ph
1=3phase , 2=1/3ph , 3=1ph or 5=1ph+1*3ph .
t1 1Ph will be used. If input signal TR3P is activated in
1MRK 506 326-UUS B
timer
3PT1TO
PULSE
Blocking out
OR
STBRREC (79)
State Control
COUNTER
Shot 0
0
CL
Shot 1
1
Shot 2
2
Shot 3
3
Shot 4
R
4
Shot 5
5
INPROGR
PREP3P
ANSI10000257.vsd
GUID-8B6F7253-294F-48D2-8664-E711B59E2CC4 v1
GUID-F408190D-F710-42BF-9737-2ACEEBB38883 v1
t1 1Ph , t1 3Ph . If no
Line distance protection REL650
Technical manual