Section 8
Frequency protection
Table 189: SAPTUF (81) Output signals
Name
TRIP
PICKUP
RESTORE
BLKDMAGN
8.1.5
Settings
Table 190: SAPTUF (81) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PUFrequency
35.00 - 75.00
tDelay
0.000 - 60.000
tRestore
0.000 - 60.000
RestoreFreq
45.00 - 65.00
8.1.6
Monitored data
Table 191: SAPTUF (81) Monitored data
Name
FREQ
8.1.7
Operation principle
Underfrequency protection (SAPTUF, 81) function is used to detect low power system frequency. If
the frequency remains below the set value for a time period corresponding to the chosen time
delay, the corresponding trip signal is issued. To avoid an unwanted trip due to uncertain
frequency measurement at low voltage magnitude, a voltage controlled blocking of the function is
available from the preprocessing function, that is, if the voltage is lower than the set blocking
voltage in the preprocessing function, the function is blocked and no PICKUP or TRIP signal is
issued.
8.1.7.1
Measurement principle
The fundamental frequency of the measured input voltage is measured continuously, and
compared with the set value,
magnitude. If the voltage magnitude decreases the setting
preprocessing function, which is set as a percentage of a global base voltage parameter, SAPTUF
256
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
General pickup signal
BOOLEAN
Restore signal for load restoring purposes
BOOLEAN
Measurement blocked due to low voltage amplitude
Unit
Step
-
-
Hz
0.01
s
0.001
s
0.001
Hz
0.01
Type
Values (Range)
REAL
-
PUFrequency . The frequency function is dependent on the voltage
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
48.80
Frequency set value
0.200
Operate time delay
0.000
Restore time delay
49.90
Restore frequency if frequency is above
frequency value
Unit
Description
Hz
Measured frequency
MinValFreqMeas in the SMAI
1MRK 506 326-UUS B
PID-1969-OUTPUTSIGNALS v6
PID-1969-SETTINGS v6
PID-1969-MONITOREDDATA v8
M13354-3 v4
M13354-6 v4
Line distance protection REL650
Technical manual