Section 13
Monitoring
13.16.7
Technical data
Table 435: SSIML(71) Technical data
Function
Alarm, oil level
Oil level lockout
Temperature alarm
Temperature lockout
Timers
13.17
Circuit breaker condition monitoring SSCBR
13.17.1
Identification
Function description
Circuit breaker condition monitoring
13.17.2
Functionality
The circuit breaker condition monitoring function SSCBR is used to monitor different parameters
of the circuit breaker. The breaker requires maintenance when the number of operations has
reached a predefined value. For proper functioning of the circuit breaker, it is essential to monitor
the circuit breaker operation, spring charge indication, breaker wear, travel time, number of
operation cycles and accumulated energy. The energy is calculated from the measured input
currents as a sum of I
threshold settings.
The function contains a blocking functionality. It is possible to block the function outputs, if
desired.
488
Range or value
0.00-25.00
0.00-25.00
-40.00-200.00
-40.00-200.00
(0.000-60.000) s
IEC 61850
identification
SSCBR
^
2 t values. Alarms are generated when the calculated values exceed the
© Copyright 2011 ABB Power Grids. All rights reserved
Accuracy
-
-
-
-
± 0.5% ± 110 ms
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Line distance protection REL650
1MRK 506 326-UUS B
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v2
GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v5
GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v7
Technical manual