Section 7
Voltage protection
7.1.4
Signals
Table 164: UV2PTUV (27) Input signals
Name
V3P
BLOCK
BLK1
BLK2
Table 165: UV2PTUV (27) Output signals
Name
TRIP
TRST1
TRST2
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
7.1.5
Settings
Table 166: UV2PTUV (27) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationStep1
Disabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
OpMode1
1 out of 3
2 out of 3
3 out of 3
Pickup1
1 - 100
t1
0.00 - 6000.00
t1Min
0.000 - 60.000
Table continues on next page
234
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of step 1
BOOLEAN
0
Block of step 2
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Trip signal from step 1
BOOLEAN
Trip signal from step 2
BOOLEAN
General pickup signal
BOOLEAN
Start signal from step 1
BOOLEAN
Pick up signal from step 1 phase A
BOOLEAN
Pick up signal from step 1 phase B
BOOLEAN
Pick up signal from step 1 phase C
BOOLEAN
Start signal from step 2
Unit
Step
-
-
-
-
-
-
-
-
%VB
1
s
0.01
s
0.001
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
Enabled
Enable execution of step 1
Definite time
Selection of time delay curve type for step
1
1 out of 3
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 1
70
Voltage start value (DT & IDMT) in % of
VBase for step 1
5.00
Definite time delay of step 1
5.000
Minimum operate time for inverse curves
for step 1
1MRK 506 326-UUS B
PID-2720-INPUTSIGNALS v5
PID-2720-OUTPUTSIGNALS v5
PID-2720-SETTINGS v5
Line distance protection REL650
Technical manual