ABB Relion 650 Series Technical Manual page 364

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 11
Scheme communication
Name
WEIBLK2
LOVBZ
CBOPEN
CRL
Table 293: ECRWPSCH (85) Output signals
Name
IRVL
TRWEI
ECHO
CR
11.5.5
Settings
Table 294: ECRWPSCH (85) Group settings (basic)
Name
Values (Range)
CurrRev
Disabled
Enabled
tPickUpRev
0.000 - 60.000
tDelayRev
0.000 - 60.000
WEI
Disabled
Echo
Echo & Trip
tPickUpWEI
0.000 - 60.000
3V0PU
5 - 70
Table 295: ECRWPSCH (85) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
358
Type
Default
Description
BOOLEAN
0
Block of WEI logic due to operation of other protections that
would effect a pilot trip or the detection of reverse faults that will
be tripped by an external device
BOOLEAN
0
Block of trip from WEI logic through the loss of voltage (fuse-
failure) function
BOOLEAN
0
Block of trip from WEI logic by an open breaker
BOOLEAN
0
POTT or Unblock carrier receive for WEI logic
Type
Description
BOOLEAN
Operation of current reversal logic
BOOLEAN
Trip of WEI logic
BOOLEAN
A signal that indicates channel start (CS) by WEI logic
BOOLEAN
POR Carrier signal received from remote end
Unit
Step
-
-
s
0.001
s
0.001
-
-
s
0.001
%VB
1
Unit
Step
-
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operating mode of Current Reversal Logic
0.020
Pickup time for current reversal logic
0.060
Time Delay to prevent Carrier send and
local trip
Disabled
Operating mode of WEI logic
0.000
Coordination time for the WEI logic
25
Neutral voltage setting for fault conditions
measurement
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 326-UUS B
PID-1622-OUTPUTSIGNALS v5
PID-1622-SETTINGS v5
Line distance protection REL650
Technical manual