ABB Relion 650 Series Technical Manual page 235

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
6.16.4
Signals
Table 158: DNSPTOC (46) Input signals
Name
I3P
V3P
BLOCK
BLKOC1
ENMLTOC1
BLKOC2
ENMLTOC2
Table 159: DNSPTOC (46) Output signals
Name
TRIP
TROC1
TROC2
BFI_3P
PU_OC1
PU_OC2
DIROC1
DIROC2
Current
VOLTAGE
VIANGLE
6.16.5
Settings
Table 160: DNSPTOC (46) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
RCADir
-180 - 180
ROADir
1 - 90
LowVolt_VM
0.0 - 5.0
Table continues on next page
Line distance protection REL650
Technical manual
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of over current function OC1
BOOLEAN
0
Enable signal for current multiplier - step1 (OC1)
BOOLEAN
0
Block of over current function OC2
BOOLEAN
0
Enable signal for current multiplier - step 2 (OC2)
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Trip signal from step 1 (OC1)
BOOLEAN
Trip signal from step 2 (OC2)
BOOLEAN
General pickup signal
BOOLEAN
OC1_PICK UP
BOOLEAN
OC2_PICK UP
INTEGER
Directional mode of step 1 (non-directional, forward, reverse)
INTEGER
Directional mode of step 2 (non-directional, forward, reverse)
REAL
Measured current value
REAL
Measured voltage value
REAL
Angle between voltage and current
Unit
Step
-
-
Deg
1
Deg
1
%VB
0.1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
-75
Relay characteristic angle
75
Relay operate angle
0.5
Voltage level in % of Vbase below which
ActLowVolt control takes over
Section 6
Current protection
PID-1833-INPUTSIGNALS v5
PID-1833-OUTPUTSIGNALS v5
PID-1833-SETTINGS v5
229