Section 13
Monitoring
13.12
Measured value expander block MVEXP
13.12.1
Identification
Function description
Measured value expander block
13.12.2
Functionality
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic
communication I/O functions (MVGGIO) are provided with measurement supervision functionality.
All measured values can be supervised with four settable limits: low-low limit, low limit, high limit
and high-high limit. The measure value expander block has been introduced to enable translating
the integer output signal from the measuring functions to 5 binary signals: below low-low limit,
below low limit, normal, above high-high limit or above high limit. The output signals can be used
as conditions in the configurable logic or for alarming purpose.
13.12.3
Function block
RANGE*
IEC09000215 V1 EN-US
Figure 244: MVEXP function block
13.12.4
Signals
Table 412: MVEXP Input signals
Name
RANGE
470
IEC 61850
identification
MVEXP
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC09000215-1-en.vsd
Type
Default
INTEGER
0
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 60617
identification
MVEXP
-
Description
Measured value range
1MRK 506 326-UUS B
GUID-4B87D3B1-D6A9-4C09-801D-AB952BB1ED44 v2
ANSI/IEEE C37.2
device number
-
GUID-8AFC0AEF-A8D9-4F31-873C-51FF237D540C v1
PID-1824-INPUTSIGNALS v9
Line distance protection REL650
Technical manual
SEMOD52450-4 v5
SEMOD54336-4 v3