ABB Relion 650 Series Technical Manual page 393

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block B16I
Name of input
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16) are active
that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the
B16I function block.
12.7
Boolean 16 to integer conversion with logic node
representation B16IFCVI
12.7.1
Identification
Function description
Boolean 16 to integer conversion
with logic node representation
12.7.2
Functionality
Boolean 16 to integer conversion with logic node representation function (B16IFCVI) is used to
transform a set of 16 binary (logical) signals into an integer.
Line distance protection REL650
Technical manual
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
IEC 61850
identification
B16IFCVI
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
Input 5
16
Input 6
32
Input 7
64
Input 8
128
Input 9
256
Input 10
512
Input 11
1024
Input 12
2048
Input 13
4096
Input 14
8192
Input 15
16384
Input 16
32768
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 12
Logic
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
SEMOD175757-2 v3
SEMOD175781-4 v4
387