ABB Relion 650 Series Technical Manual page 91

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Table 21:
Name
TRIP
PICKUP
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
NDIR_A
NDIR_B
NDIR_C
NDIR_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
STCNDZI
DLECND
5.2.5
Settings
Table 22:
FDPSPDIS Group settings (basic)
Name
Values (Range)
21 enable
Disabled
Enabled
50/51 enable
Disabled
Enabled
3I0BLK_PP
10 - 100
3I0Enable_PG
10 - 100
RLdFwd
1.00 - 3000.00
RldRev
1.00 - 3000.00
Table continues on next page
Line distance protection REL650
Technical manual
FDPSPDIS Output signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INTEGER
INTEGER
Unit
-
-
%IPh
%IPh
ohm/p
ohm/p
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Trip by pilot communication scheme logic
Start in any phase or loop
Fault detected in phaseA - forward direction
Fault detected in phase B - forward direction
Fault detected in phase C - forward direction
Ground fault detected in forward direction
Fault detected in phase A- reverse direction
Fault detected in phase B - reverse direction
Fault detected in phase C - reverse direction
Ground fault detected in reverse direction
Non directional fault detected in Phase A
Non directional fault detected in Phase B
Non directional fault detected in Phase C
Non directional start, Phase-Ground
Single phase-to-ground fault in forward direction
Phase-to-phase fault in forward direction
Pick up in forward direction for three-phase fault
Current conditions release of Phase-Ground measuring elements
Current conditions release of Phase-Phase measuring elements
Pick up condition (Z< with LE and/or I> and 3I0 E/F detection)
Pickup for load encroachment and 3I0
Step
Default
-
Enabled
-
Disabled
1
40
1
20
0.01
80.00
0.01
80.00
Impedance protection
Description
Operation of impedance based
measurement
Operation of current based measurement
3I0 limit for blocking Phase-to-Phase
measuring loops
3I0 limit for releasing Phase-to-Ground
measuring loops
Forward resistive reach for the load
impedance area
Reverse resistive reach for the load
impedance area
Section 5
PID-1538-OUTPUTSIGNALS v6
PID-1538-SETTINGS v8
85