1MRK 506 326-UUS B
5.7.6.5
Operating and inhibit conditions
Figure
81
(68).
The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh = Disabled , but notice that the DFw and DRv will still be calculated from RLdOutFw
RLdOutRv . The characteristic will in this case be only quadrilateral.
and
There are three different ways to form the internal INHIBIT signal:
Logical 1 on functional input BLOCK inhibits the output PICKUP signal instantaneously.
The INHIBIT internal signal is activated, if the power swing has been detected and the
measured impedance remains within its operate characteristic for the time, which is longer
than the time delay set on
logical 1 signal to the BLK_SS functional input.
The INHIBIT internal signal is activated after the time delay, set on
appears during the power swing (input IOCHECK is high) and the power swing has been
detected before the ground-fault (activation of the signal I0CHECK). It is possible to disable
this condition by connecting the logical 1 signal to the BLK_I0 functional input.
5.7.7
Technical data
Table 53:
Function
Reactive reach
Resistive reach
Timers
Minimum operate current
5.8
Automatic switch onto fault logic, voltage and current
based ZCVPSOF
5.8.1
Identification
Function description
Automatic switch onto fault logic,
voltage and current based
Line distance protection REL650
Technical manual
presents a simplified logic diagram for the Power swing detection function ZMRPSB
tR2 timer. It is possible to disable this condition by connecting the
ZMRPSB (68) technical data
Range or value
(0.10-3000.00) W
(0.10–1000.00)W
(0.000-60.000) s
(5-30) of IBase
© Copyright 2011 ABB Power Grids. All rights reserved
Accuracy
± 2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x V
Current range: (0.5-30) x I
Angle: at 0 degrees and 85 degrees
± 0.5% ± 25 ms
± 1% of I
IEC 61850
IEC 60617
identification
identification
ZCVPSOF
-
Impedance protection
tR1 timer, if an ground-fault
n
n
n
ANSI/IEEE C37.2
device number
-
Section 5
M13877-38 v4
M16036-1 v5
SEMOD155890-2 v2