Section 6
Current protection
Table 133: CCRPLD (52PD) Output signals
Name
TRIP
PICKUP
6.13.5
Settings
Table 134: CCRPLD (52PD) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tTrip
0.000 - 60.000
ContactSel
Disabled
PD signal from CB
CurrentSel
Disabled
CB oper monitor
Continuous
monitor
CurrUnsymPU
0 - 100
CurrRelPU
0 - 100
Table 135: CCRPLD (52PD) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.13.6
Monitored data
Table 136: CCRPLD (52PD) Monitored data
Name
IMin
IMax
6.13.7
Operation principle
The detection of pole discrepancy can be made in two different ways. If the contact based
function is used an external logic can be made by connecting the auxiliary contacts of the circuit
breaker so that a pole discrepancy is indicated, see figure 113.
214
Type
Description
BOOLEAN
Trip signal to CB
BOOLEAN
Trip condition TRUE, waiting for time delay
Unit
Step
-
-
s
0.001
-
-
-
-
%
1
%IB
1
Unit
Step
-
1
Type
Values (Range)
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
0.300
Time delay between trip condition and trip
signal
Disabled
Contact function selection
Disabled
Current function selection
80
Unsym magn of lowest phase current
compared to the highest.
10
Current magnitude for release of the
function in % of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
Unit
Description
A
Lowest phase current
A
Highest phase current
1MRK 506 326-UUS B
PID-1167-OUTPUTSIGNALS v5
PID-1167-SETTINGS v5
PID-1167-MONITOREDDATA v6
M13273-3 v5
Line distance protection REL650
Technical manual