ABB Relion 650 Series Technical Manual page 331

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
10.6.3
Function block
BLOCK
PSTO
IPOS1
IPOS2
IEC09000341 V1 EN-US
10.6.4
Signals
Table 247: VSGGIO Input signals
Name
BLOCK
PSTO
IPOS1
IPOS2
Table 248: VSGGIO Output signals
Name
BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21
10.6.5
Settings
Table 249: VSGGIO Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CtlModel
Dir Norm
SBO Enh
Mode
Steady
Pulsed
tSelect
0.000 - 60.000
tPulse
0.000 - 60.000
Line distance protection REL650
Technical manual
VSGGIO
BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21
IEC09000341-1-en.vsd
Type
Default
BOOLEAN
0
INTEGER
0
BOOLEAN
0
BOOLEAN
0
Type
BOOLEAN
INTEGER
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
-
-
-
-
-
-
s
0.001
s
0.001
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Block of function
Operator place selection
Position 1 indicating input
Position 2 indicating input
Description
The function is active but the functionality is blocked
Position indication, integer
Position 1 indication, logical signal
Position 2 indication, logical signal
Execute command from position 1 to position 2
Execute command from position 2 to position 1
Default
Description
Disabled
Disable/Enable Operation
Dir Norm
Specifies the type for control model
according to IEC 61850
Pulsed
Operation mode
30.000
Max time between select and execute
signals
0.200
Command pulse lenght
Section 10
Control
GUID-3C15E653-9FD5-4712-8DBD-77E26319F295 v1
PID-1825-INPUTSIGNALS v5
PID-1825-OUTPUTSIGNALS v5
PID-1825-SETTINGS v5
325