ABB Relion 650 Series Technical Manual page 230

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Current protection
Name
PICKUP2
P
PPERCENT
Q
QPERCENT
6.15.3.4
Settings
Table 152: GUPPDUP (37) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpMode1
Disabled
UnderPower
Power1
0.0 - 500.0
Angle1
-180.0 - 180.0
TripDelay1
0.010 - 6000.000
OpMode2
Disabled
UnderPower
Power2
0.0 - 500.0
Angle2
-180.0 - 180.0
TripDelay2
0.010 - 6000.000
Table 153: GUPPDUP (37) Group settings (advanced)
Name
Values (Range)
TD
0.00 - 0.99
Table 154: GUPPDUP (37) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
224
Type
Description
BOOLEAN
Pickup signal from stage 2
REAL
Active Power
REAL
Active power in % of calculated power base value
REAL
Reactive power
REAL
Reactive power in % of calculated power base value
Unit
Step
-
-
-
-
%
0.1
Deg
0.1
s
0.001
-
-
%
0.1
Deg
0.1
s
0.001
Unit
Step
-
0.01
Unit
Step
-
1
-
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Disable / Enable
UnderPower
Operation mode 1
1.0
Power setting for stage 1 in % of
calculated power base value
0.0
Characteristic angle for stage 1
1.000
Trip delay for stage 1
UnderPower
Operation mode 2
1.0
Power setting for stage 2 in % of
calculated power base value
0.0
Characteristic angle for stage 2
1.000
Trip delay for stage 2
Default
Description
0.00
Low pass filter coefficient for power
measurement, V and I
Default
Description
1
Selection of one of the Global Base Value
groups
Pos Seq
Mode of measurement for current and
voltage
1MRK 506 326-UUS B
PID-2724-SETTINGS v5
Line distance protection REL650
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650