ABB Relion 650 Series Technical Manual page 247

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Name
Values (Range)
t1Min
0.000 - 60.000
TD1
0.05 - 1.10
OperationStep2
Disabled
Enabled
OpMode2
1 out of 3
2 out of 3
3 out of 3
Pickup2
1 - 200
t2
0.000 - 60.000
Table 173: OV2PTOV (59) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
ConnType
PhN DFT
PhN RMS
PhPh DFT
PhPh RMS
7.2.6
Monitored data
Table 174: OV2PTOV (59) Monitored data
Name
V_A
V_B
V_C
7.2.7
Operation principle
Two step overvoltage protection OV2PTOV (59) is used to detect high power system voltage.
OV2PTOV (59) has two steps with separate time delays. If one-, two- or three-phase voltages
increase above the set value, a corresponding PICKUP signal is issued. OV2PTOV (59) can be set to
PICKUP/TRIP, based on
the set point. If the voltage remains above the set value for a time period corresponding to the
chosen time delay, the corresponding trip signal is issued.
The time delay characteristic is settable for step 1 and can be either definite or inverse time
delayed. Step 2 is always definite time delayed.
The voltage related settings are made in percent of the global set base voltage
in kV, phase-to-phase.
Line distance protection REL650
Technical manual
Unit
Step
s
0.001
-
0.01
-
-
-
-
%VB
1
s
0.001
Unit
Step
-
1
-
-
Type
Values (Range)
REAL
-
REAL
-
REAL
-
1 out of 3 , 2 out of 3 or 3 out of 3 of the measured voltages, being above
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
5.000
Minimum operate time for inverse curves
for step 1
0.05
Time multiplier for the inverse time delay
for step 1
Enabled
Enable execution of step 2
1 out of 3
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 2
150
Voltage start value (DT & IDMT) in % of
VBase for step 2
5.000
Definite time delay of step 2
Default
Description
1
Selection of one of the Global Base Value
groups
PhN DFT
Group selector for connection type
Unit
Description
kV
Voltage in phase A
kV
Voltage in phase B
kV
Voltage in phase C
Section 7
Voltage protection
PID-2719-MONITOREDDATA v5
M15330-3 v5
VBase , which is set
241