1MRK 506 326-UUS B
13.17.3
Function block
I3P*
BLOCK
BLK_ALM
POSOPEN
POSCLOSE
ALMPRES
LOPRES
SPRCHRGN
SPRCHRGD
CBCNTRST
IACCRST
SPCHTRST
TRVTRST
ANSI10000281 V1 EN-US
Figure 252: SSCBR function block
13.17.4
Signals
Table 436: SSCBR Input signals
Name
I3P
BLOCK
BLK_ALM
POSOPEN
POSCLOSE
ALMPRES
LOPRES
SPRCHRGN
SPRCHRGD
CBCNTRST
IACCRST
SPCHTRST
TRVTRST
Table 437: SSCBR Output signals
Name
TRVTOAL
TRVTCAL
SPRCHRAL
OPRALM
Table continues on next page
Line distance protection REL650
Technical manual
SSCBR
TRVTOAL
TRVTCAL
SPRCHRAL
OPRALM
OPRLOALM
IACCALM
IACCLOAL
CBLIFEAL
NOOPRALM
PRESALM
PRESLO
CBOPEN
CBINVPOS
52a
ANSI10000281-1-en.vsd
Type
Default
GROUP
-
SIGNAL
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Three phase group signal for current inputs
Block of function
Block all the alarms
Signal for open position of apparatus from I/O
Signal for close position of apparatus from I/O
Binary pressure alarm input
Binary pressure input for lockout indication
CB spring charging started input
CB spring charged input
Reset input for CB remaining life and operation counter
Reset accumulated currents power
Reset spring charge time
Reset travel time
Description
CB open travel time exceeded set value
CB close travel time exceeded set value
Spring charging time has crossed the set value
Number of CB operations exceeds alarm limit
Section 13
Monitoring
GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v8
PID-1832-INPUTSIGNALS v5
PID-1832-OUTPUTSIGNALS v5
489