Default Operation Parameter Settings - ABB ProKiln GAC400 Operating Instruction

Probe gas sampling system
Table of Contents

Advertisement

30
ProKiln GAC400 PROBE GAS SAMPLING SYSTEM | OI/GAC400-EN REV. A
... 3 Design and function
... Access permissions
By selecting 'change password' the following dialog will pop-up
and a new password can be created.
Figure 20: User dialog for changing the password

Default operation parameter settings

Parameter input cooling menu
Figure 21: Cooling menu
Parameter input
Function
Start
Start temperature for hysteresis
control of water cooler fan
Stop
Stop temperature for hysteresis
control of water cooler fan
See Parameter input Alarm setpoint
Flow
menu on page 33 for alarm limits for
water flow OK
Parameter input analysis menu
Figure 22: Analysis menu
Parameter input
Function
Analyse Time
The time for each sampling period
before probe cleaning
Cleaning before
The number of cleanings to take place
retraction
before the retractor automatically
retracts the probe from the kiln and
inserts it back again
Default value
75 °C (167 °F)
70 °C (158 °F)
80 l/min
(21.13 gal US/min)
Default value
15 min
10 times
(Every 2,5 hours)