Section 21
Time inverse characteristics
æ
ç
ç
[ ]
s
=
t
ç
æ
ç
ç
ç
è
è
EQUATION1640 V1 EN-US
where:
p, A, B, C
Pickupn
td
i
For inverse time characteristics a time will be initiated when the current reaches the set pickup
level. From the general expression of the characteristic the following can be seen:
(
-
×
t
B td
op
EQUATION1642 V1 EN-US
where:
t
op
The time elapsed to the moment of trip is reached when the integral fulfils according to
equation 99, in addition to the constant time delay:
t
æ
æ
ò
i
ç
ç
ç
è
Pickupn
è
0
EQUATION1643 V1 EN-US
For the numerical protection the sum below must fulfil the equation for trip.
604
ö
÷
A
÷
+
B
×
td
÷
P
ö
i
÷
-
÷
C
÷
ø
ø
Pickupn
æ
ö
P
)
æ
ö
i
× ç
÷ =
-
ç
÷
C
A td
ç
÷
è
ø
Pickupn
è
ø
is the operating time of the protection
ö
P
ö
÷
-
×
³
×
÷
C
dt
A td
÷
ø
ø
© Copyright 2011 ABB Power Grids. All rights reserved
are constants defined for each curve type,
is the set pickup current for step n,
is set time multiplier for step n and
is the measured current.
×
1MRK 506 326-UUS B
(Equation 97)
(Equation 98)
(Equation 99)
Line distance protection REL650
Technical manual