ABB Relion 650 Series Technical Manual page 311

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Name
CLOSECMD
WFMASTER
COUNT1P
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
10.3.5
Settings
Table 231: STBRREC (79) Group settings (basic)
Name
Values (Range)
Operation
Disabled
External ctrl
Enabled
ARMode
3 phase
1/3ph
1 phase
1ph+1*3ph
t1 1Ph
0.000 - 60.000
t1 3Ph
0.000 - 60.000
tReset
0.00 - 6000.00
tSync
0.00 - 6000.00
tTrip
0.000 - 60.000
tCBClosedMin
0.00 - 6000.00
tUnsucCl
0.00 - 6000.00
Priority
None
Low
High
tWaitForMaster
0.00 - 6000.00
Line distance protection REL650
Technical manual
Type
Description
BOOLEAN
Closing command for CB
BOOLEAN
Signal to Slave issued by Master for sequential reclosing
INTEGER
Counting the number of single-phase reclosing shots
INTEGER
Counting the number of three-phase reclosing shot 1
INTEGER
Counting the number of three-phase reclosing shot 2
INTEGER
Counting the number of three-phase reclosing shot 3
INTEGER
Counting the number of three-phase reclosing shot 4
INTEGER
Counting the number of three-phase reclosing shot 5
INTEGER
Counting total number of reclosing shots
Unit
Step
-
-
-
-
s
0.001
s
0.001
s
0.01
s
0.01
s
0.001
s
0.01
s
0.01
-
-
s
0.01
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
External ctrl
Disable/ExternalCtrl/Enable
3 phase
AR mode selection e.g. 3ph, 1/3ph
1.000
Open time for shot 1, single-phase
6.000
Open time for shot 1, delayed reclosing
3ph
60.00
Duration of the reset time
30.00
Maximum wait time for synchronism-check
OK
0.200
Maximum trip pulse duration
5.00
Minimum time that CB must be closed
before new sequence allows
30.00
Wait time for CB before indicating
Unsuccessful/Successful
None
Priority selection between adjacent
terminals None/Low/High
60.00
Maximum wait time for release from
Master
Section 10
Control
PID-2350-SETTINGS v7
305